TRACEABLE CALIBRATION OF POWER HARMONICS AND FLICKER ANALYSERS
Abstract
The paper describes a precision measurement system developed at NML for the calibration of three-phase instruments measuring harmonics of current up to 16 A, voltage fluctuation and flicker. Particular attention is given to establishing a traceable link to the Australian primary standards of electrical quantities. Current and voltage harmonics up to the 99<sup>th</sup> and fluctuating voltages can be generated and measured with relative uncertainties close to 1·10<sup>-5</sup>.
Event details
- Event
- XVII IMEKO World Congress
- Place
- Dubrovnik, CROATIA
- Time
- 22 June 2003 - 28 June 2003
- Website