Skip to main content

The Importance of the Short-Circuit Impedance Measurement To the Operation of the Transformer Units

Traian Chiulan, Brândusa Pantelimon

Abstract

Knowledge of the short-circuit impedance variation is necessary for verifying the observance of the technical conditions (including the design conditions), certain nonconformities in the winding execution, checking the winding behavior in operation, verifying the system and short-circuit calculation (including the correct protection setup), the loading of the same type units, or more importantly, of the different type ones.
The measurement of the short-circuit impedance by means of a three phase low voltage power source can be performed because the value of impedances does not depend on the applied voltage. ICEMENERG has developed a modern measurement system that has been used for performing a great amount of measurements, the results of which have been compared with those of the manufacturer’s, and with those obtained by means of high voltage measurements.

Download
IMEKO-TC4-2007-014.pdf
DOI
-
IMEKO TC
TC4 - Measurement of Electrical Quantities

Event details

Event
TC4 Symposium 2007
Technical Committee
TC4
Place
Iasi, ROMANIA
Download
TC4CallForPapers.pdf
Time
19 September 2007 - 21 September 2007
Website
http://www.imeko2007.ee.tuiasi.ro/

Back to the proceedings