HARMONICS MEASUREMENT METHOD USING A DSP BASED ASIC
Abstract
A compact, low cost harmonics measurement equipment, harmonics monitorTM, has been developed using a DSP based mixed signal ASIC. Each effective current harmonics from the basic frequency up to the 19<sup>th</sup> order harmonics and the total harmonics distortion ratio can be obtained in real time. In stead of using a conventional FFT method a 6<sup>th</sup> order, digital IIR filtering method was used for the accurate measurement. It allowed the computation to be in real time and the configuration of the main circuitry to be simplified into a single chip, thereby reducing the system cost. To compensate gain drop of ADC outputs over a continuous wide range of frequency the second order equalizing digital IIR filter was applied as well. The measurement accuracy has been realized within ± 0.5% of full scale from the basic frequency up to 19th order harmonics frequency.
Event details
- Event
- XVI IMEKO World Congress
- Place
- Vienna, AUSTRIA
- Time
- 25 September 2000 - 28 September 2000