Skip to main content

Laboratory reproduction of on-field low power quality conditions for the calibration/verification of electrical energy meters

Alessandro Cultrera, Gabriele Germito, Danilo Serazio, Flavio Galliana, Bruno Trinchera, Giulia Aprile, Martino Chirulli, Luca Callegaro

Abstract

In this work we present a method for testing static active energy meters in low power quality conditions recorded at installation sites. Voltage and current waveforms recorded on the field with a calibrated portable instrument were reproduced with an accurate phantom power generator up to the 40th harmonic. The error on the active energy measurement of an energy meter under test (WDUT) in conditions reproduced from the on-field measurements was evaluated in comparison with a reference meter (WREF). On-field data were recorded at a 50 kW self production photovoltaic facility. This method allows the laboratory reproduction of realistic (distorted) on-field conditions in a metrologically traceable framework.

Download
IMEKO-TC4-2022-06.pdf
DOI
10.21014/tc4-2022.06
IMEKO TC
TC4 - Measurement of Electrical Quantities

Event details

Event
TC4 Symposium 2022
Technical Committee
TC4
Email
info@imeko-tc4-2022.org
Place
Brescia, ITALY
Time
12 September 2022 - 14 September 2022
Website
http://www.imeko-tc4-2022.org/
Proceedings
https://www.imeko.org/publications/tc4-2022

Back to the proceedings