Skip to main content

Temperature Rise in MV Switchgears: the Role of Loose Busbar Joints

Susanna Spinsante, Grazia Iadarola, Gianmarco Mazzocchi, Claudio Romagnoli

Abstract

The identification of the different causes of a Medium Voltage (MV) switchgear failure is a complex task. Among the conditions contributing to failure, thermal cycling due to loose joints and electrical components may act as a trigger for fault. This paper presents an experimental analysis of temperature variation taking place in 27 different points of a MV switchgear and originating from loose mechanical and electrical joints in the busbars, compared to the normal operating condition. The loose joints - due to improper installation, vibrations, or ageing of components - are obtained by applying a controlled clamping below the recommended operational value of 45 Nm torque, to six busbar joint screws (two for each phase). Results show that when the applied clamping goes below 10% of the recommended value, temperature does not rise significantly in points other than the loose ones, while the main circuits exhibit a detectable variation of their electrical resistance.

Download
IMEKO-TC4-2022-10.pdf
DOI
10.21014/tc4-2022.10
IMEKO TC
TC4 - Measurement of Electrical Quantities

Event details

Event
TC4 Symposium 2022
Technical Committee
TC4
Email
info@imeko-tc4-2022.org
Place
Brescia, ITALY
Time
12 September 2022 - 14 September 2022
Website
http://www.imeko-tc4-2022.org/
Proceedings
https://www.imeko.org/publications/tc4-2022

Back to the proceedings