COMPARATIVE STUDY ON CHOSEN METHODS OF VOLTAGE DIP TRACKING BASED ON REAL EXAMPLE

Tomasz Tarasiuk
Abstract:
The paper presents results of experimental study of two methods of voltage dip tracking. First is based on half cycle absolute peak value monitoring, whereas second is based on low-pass filtration of squares of voltage samples. Both methods are devised for application in low-cost integrated circuits, dedicated to power quality monitoring. The real voltage dip has been considered for the aim. The results have been compared with reference method recommended in IEC Std. 61000-4-30.
Keywords:
voltage dip, low-cost measurement, power quality
Download:
IMEKO-WC-2015-TC4-153.pdf
DOI:
-
Event details
Event name:
XXI IMEKO World Congress
Title:

Measurement in Research and Industry

Place:
Prague, CZECH REPUBLIC
Time:
30 August 2015 - 04 September 2015